Standard Sensor
H = 5.95 - pipe wall thickness - (0.10 X I.D.)
Example:
3.0 inch schedule 80 wrought steel;
Wall thickness= 0.3 in.
Inside diameter = 2.9 in.
H = 5.95 - 0.3 - (0.10 X 2.9)
H = 5.36 in.
Hot-Tap Sensor
H = 15.00 - pipe wall thickness - (0.10 X I.D.)
Example:
10 inch schedule 40 wrought steel;
Wall thickness= 0.365 in.
Inside diameter = 10.02 in.
H = 15.00 - 0.365 - (0.10 X 10.02)
H = 13.633 in.
"H"
alignment rod
sensor flange
process pipe
direction of flow
pipe side view
process pipe (side view)
direction of flow
alignment rod
"H"
protector plate
Record your pipes "H"
dimension for future
reference:
H= _________________
Record your pipes "H"
dimension for future
reference:
H= _________________